600/1000V, XLPE Insulated Cables according to IEC 60502-1

Affiliate classification
Quantity
-
+
没有此类产品
Detail
Application:
This type of cable is mainly used for the power supply of the mortgage installation system. It can be installed indoors or outdoors. It can be laid in cable ducts or directly buried. It can be used in substations, industrial areas and other places without mechanical damage.
Construction:
Conductors:
Copper or Aluminum conductor, round stranded or Shaped, Class 2 to IEC 60228, BS EN 60228. For smaller sizes, a solid round conductor, Class 1 as per IEC 60228, BS EN 60228 can also be supplied upon request.
Insulation:
XLPE insulation, thickness in accordance with IEC 60502, BS 5467. Continuous operating temperature is 85 ° C
Assembly/ Inner Sheath
Two, Three or Four insulated conductors are laid-up together with non-hygroscopic
fillers and the assembly is bedded with an extruded layer of PVC. In case of non armored cables, this layer may be omitted
Armor
Aluminum/Galvanized Steel Wires applied helically over the bedding as per IEC60502 or as per BS 5467, BS 6346. Single core cables shall be Aluminum wire armor. Aluminum/Steel Tapes applied helically over the bedding of multi-core cables as per IEC 60502.
Outer Sheath
Outer sheath shall be of Extruded PVC Type ST2 as per IEC 60502-1 or Type 9 as BS 6346/5467.
Special type of PVC sheathing material such as Fire Retardant PVC, Anti-Termite PVC, Anti-Rodent PVC, Sunlight resistant PVC, Oil Resistant PVC are available on special request. Also, special sheathing materials such as LLDPE, MDPE, HDPE,LSF, CPE are available on request.
Fire Performance of Cable Sheaths
Cables can be supplied with special flame retardant PVC outer sheath to comply with the flame test requirements of IEC 60332-3-22, IEC 60332-3-23 and IEC 60332-3-24,can also supply cables with Low Smoke Halogen Free (LSHF) material according to IEC 60502-1, BS 7211, BS 6724 or other equivalent standards
 
Cable Parameters:
 
Single core(unarmored)
 

Nominal Area

mm²

Reference

conductor Diameter

mm

Nominal Insulation thickness

mm

Nominal Sheath thickness

mm

Reference. Overall Diameter

mm

Reference. Weight

Kg/Km

1x1.5

1.6

0.7

1.4

6

50

1x2.5

2

0.7

1.4

6.5

70

1x4

2.6

0.7

1.4

7

80

1x6

3.1

0.7

1.4

7.5

110

1x10

4

0.7

1.4

8.5

150

1x16

5

0.7

1.4

9.5

215

1x25

6.3

0.9

1.4

11.5

315

1x35

7.4

0.9

1.4

12

415

1x50

8.8

1

1.4

13

555

1x70

10.6

1.1

1.4

15

760

1x95

12.4

1.1

1.5

17

1025

1x120

14

1.2

1.5

18.5

1270

1x150

15.5

1.4

1.6

21.5

1575

1x185

17.4

1.6

1.6

23

1955

1x240

20.3

1.7

1.7

26

2470

1x300

22.7

1.8

1.8

28

3155

1x400

25.4

2

1.9

32

4049

1x500

28.8

2.2

2

36

5100

1x630

30.4

2.4

2.2

40

6410


TWO cores(unarmored)
 

Nominal Area

mm²

Reference

conductor Diameter

mm

Nominal Insulation thickness

mm

Nominal Sheath thickness

mm

Reference. Overall Diameter

mm

Reference. Weight

Kg/Km

2x1.5

1.6

0.7

1.8

10

125

2x2.5

2

0.7

1.8

11.5

155

2x4

2.6

0.7

1.8

12.5

195

2x6

3.1

0.7

1.8

13.5

255

2x10

4

0.7

1.8

15.5

370

2x16

5

0.7

1.8

17

500

2x25

6.3

0.9

1.8

20

700

2x35

7.4

0.9

1.8

22

900

2x50

8.8

1

1.8

25

1250

2x70

10.6

1.1

1.8

29

1600

2x95

12.4

1.1

1.9

32

2250

2x120

14

1.2

2

36

2750

2x150

15.5

1.4

2.2

40

3510

2x185

17.4

1.6

2.3

44

4200

2x240

20.3

1.7

2.5

50

5500

2x300

22.5

1.8

2.6

55

6950

2x400

25.4

2

2.9

60

8400


Three cores(unarmored)
 

Nominal Area

mm²

Reference

conductor Diameter

mm

Nominal Insulation thickness

mm

Nominal Sheath thickness

mm

Reference. Overall Diameter

mm

Reference. Weight

Kg/Km

3x1.5

1.6

0.7

1.8

10.5

150

3x2.5

2

0.7

1.8

11

190

3x4

2.6

0.7

1.8

12.5

250

3x6

3.1

0.7

1.8

14.5

320

3x10

4

0.7

1.8

15.5

465

3x16

5

0.7

1.8

18.5

670

3x25

6.3

0.9

1.8

19.5

965

3x35

7.4

0.9

1.8

22

1290

3x50

8.8

1

1.8

26

1750

3x70

10.6

1.1

1.9

28.5

2450

3x95

12.4

1.1

2

32.5

3200

3x120

14

1.2

2.1

35.5

4010

3x150

15.5

1.4

2.3

40

5050

3x185

17.4

1.6

2.4

44.5

6105

3x240

20.3

1.7

2.6

54

8050

3x300

22.5

1.8

2.7

60.5

9998


Three cores+1(unarmored)
 

Nominal Area

Reference

conductor Diameter

Nominal Insulation thickness

Nominal Sheath thickness

Reference. Overall Diameter

Reference. Weight

MM²

(3)MM

(1)MM

(3)MM

(1)MM

MM

MM

KG/KM

3x16/10

5

4

0.7

0.7

1.8

20

825

3x25/16

6.3

5

0.9

0.7

1.8

22.8

1235

3x35/16

7.4

5

0.9

0.7

1.8

24.8

1565

3x50/25

8.8

6.3

1

0.9

1.8

28.5

2220

3x70/35

10.6

7.4

1.1

0.9

1.9

32

2925

3x95/50

12.4

8.8

1.1

1

2.1

37.5

3525

3x120/70

14

10.6

1.2

1.1

2.2

41.5

4940

3x150/70

15.5

10.6

1.4

1.1

2.3

45

6250

3x185/95

17.4

12.4

1.6

1.1

2.5

50.5

7450

3x240/120

20.3

14

1.7

1.2

2.6

56

9500

3x300/150

22.7

15.5

1.8

1.4

2.8

64.5

12100


Four cores(unarmored)
 

Nominal Area

mm²

Reference

conductor Diameter

mm

Nominal Insulation thickness

mm

Nominal Sheath thickness

mm

Reference. Overall Diameter

mm

Reference. Weight

Kg/Km

4x1.5

1.6

0.7

1.8

11

170

4x2.5

2

0.7

1.8

12

230

4x4

2.6

0.7

1.8

14

305

4x6

3.1

0.7

1.8

15.5

400

4x10

4

0.7

1.8

18

585

4x16

5

0.7

1.8

20

835

4x25

6.3

0.9

1.8

22

1210

4x35

7.4

0.9

1.8

24.5

1670

4x50

8.8

1

1.8

26.5

2250

4x70

10.6

1.1

2

32

3015

4x95

12.4

1.1

2.1

36.5

4085

4x120

14

1.2

2.3

40.5

5320

4x150

15.5

1.4

2.4

44.5

6510

4x185

17.4

1.6

2.6

51

8050

4x240

20.3

1.7

2.8

58.5

10520

4x300

22.7

1.8

3

64.5

13130

 