Category
POWER CABLE
- 600/1000V, PVC Insulated Cables according to IEC 60502-1
- 600/1000V, PVC Insulated Cables according to IEC 60502-1 (armored)
- 600/1000V, XLPE Insulated Cables according to IEC 60502-1
- 600/1000V, XLPE Insulated Cables according to IEC 60502-1(armored)
- 8.7/15Kv Single Core Cables according to IEC 60502
- 8.7/15Kv Single Core Cables according to IEC 60502(armored)
- 8.7/15Kv Three Core Cables according to IEC 60502
- 8.7/15Kv Three Core Cables according to IEC 60502(armored)
- NYY-J/-O
- NYCWY
- NYCY
CONTROL CABLE
INSTRUMENTATION CABLE
ELEVATOR CABLE
HARMONIZED CODE CABLE
H07V-K,H07V-R,H07V-U
Key words:
Classification:
Product Description
Application
This product is suitable for low voltage connecting line, equipment, power distribution
room, switch cabinet for surface mounted, closed pipeline installation etc.
Implementation of standards
IEC 60227
Comply with EEC 73/23 (Low Voltage Directive) CE's.
Technical parameters
| Rated voltage | 450/750V |
| Temperature range | Flexing:-5℃~+70℃ |
| Fixed installation:-30℃~+80℃ | |
| Test voltage | AC:50HZ 2500V |
| 20℃Insulation resistance | Min 10 MΩ · km |
| Min bending radius | 12.5~15× Cable diameter |
| Production of material does not contain cadmium and silicone, free of paint. Moisture resistant properties of harmful substances, conforms to the RoHS standard. | |
| PVC self-extinguishing and flame retardant,Test method according to:IEC 60332 | |
Specification range
| Type | Cross- section (mm2) | Conductor structure (number / diameter) | Insulation Thickness (mm) | Insulation diameter (mm) | Copper weight (kg/km) | Approx weight (kg/km) |
| H07V-K | 1.5 | 48×0.2 | 0.7 | 3.1 | 14.4 | 20 |
| 2.5 | 49×0.25 | 0.8 | 3.7 | 24 | 32 | |
| 4 | 56×0.3 | 0.8 | 4.3 | 38 | 46 | |
| 6 | 84×0.3 | 0.8 | 5.0 | 58 | 64 | |
| 95 | 481×0.5 | 1.6 | 17.6 | 912 | 925 | |
| 120 | 611×0.5 | 1.6 | 19.5 | 1122 | 1152 | |
| 150 | 764×0.5 | 1.8 | 22 | 1440 | 1467 | |
| 185 | 942×0.5 | 2.0 | 24.5 | 1776 | 1820 | |
| 240 | 1222×0.5 | 2.2 | 28.2 | 2304 | 2364 |
| Type | Cross section (mm2) | Conductor structure (number / diameter) | Insulation Thickness (mm) | Insulation diameter (mm) | Copper weight (kg/km) | Approx weight (kg/km) |
| H07V-R | 1.5 | 7×0.52 | 0.7 | 3.0 | 14.4 | 23 |
| 2.5 | 7×0.68 | 0.8 | 3.6 | 24 | 35 | |
| 4 | 7×0.85 | 0.8 | 4.2 | 39 | 51 | |
| 6 | 7×1.04 | 1.0 | 5.1 | 58 | 71 | |
| 10 | 7×1.35 | 1.0 | 6.0 | 96 | 120 | |
| 16 | 7×1.7 | 1.0 | 7.1 | 154 | 170 | |
| 25 | 7×2.14 | 1.2 | 8.6 | 240 | 260 | |
| 35 | 7×2.52 | 1.2 | 10.0 | 336 | 350 | |
| 50 | 19×1.78 | 1.4 | 11.7 | 473 | 480 | |
| 70 | 19×2.14 | 1.4 | 13.5 | 672 | 680 | |
| 95 | 19×2.52 | 1.6 | 15.7 | 912 | 930 | |
| 120 | 37×2.03 | 1.6 | 17.4 | 1152 | 1160 | |
| 150 | 37×2.25 | 1.8 | 19.3 | 1430 | 1440 | |
| 185 | 37×2.52 | 2.0 | 21.6 | 1776 | 1780 | |
| 240 | 61×2.25 | 2.2 | 24.6 | 2304 | 2360 |
| Type | Cross- section (mm2) | Conductor structure (number / diameter) | Insulation Thickness (mm) | Insulation diameter (mm) | Copper weight (kg/km) | Approx weight (kg/km) |
| H07V-U | 1.5 | 48×0.2 | 0.7 | 3.1 | 14.4 | 21 |
| 2.5 | 49×0.25 | 0.8 | 3.7 | 24 | 33 | |
| 4 | 56×0.3 | 0.8 | 4.3 | 38 | 49 | |
| 6 | 84×0.3 | 0.8 | 5.0 | 58 | 69 | |
| 10 | 7×1.35 | 1 | 6.0 | 96 | 115 |